Wind turbine controller

10 October 2026 7 views View Live
Wind turbine controller

I wanted to build a wind turbine project back in college and never finished it. This is that project done properly. It's a controller for a small 300 W to 1 kW turbine charging a 12 V battery bank, like the ones that make sense on windy ridges in the hills, where the grid is weak or doesn't reach.

The one rule of wind turbines

A wind turbine must never run without a load. A solar panel with a full battery just sits there. A turbine with its load disconnected speeds up until the blades or the bearings fail. So this controller never disconnects the turbine. When the battery is full, it moves the surplus power into a dump load (a heater resistor or a water heater element) using PWM.

What it does

MeasuresHow
Wind speedCup anemometer reed switch on D2 (1 pulse per second = 0.667 m/s)
Rotor speedHall sensor and magnet on the shaft, D3, 1 pulse per revolution
Battery voltage100k / 22k divider on A0
Generator voltage100k / 10k divider on A1 (after the rectifier)
SituationAction
Battery between 14.4 and 14.8 VDump load PWM rises from 0 to 100 %, ramping about 10 % per second so the generator load never jumps
Rotor above 600 rpm for 2 sBrake
Wind above 25 m/s for 5 sBrake (storm)
Battery above 15.2 V for 10 sBrake. The dump load can't keep up, or it has failed
STOP switch onBrake at once, for maintenance
After a brakeReleased only after 5 minutes of wind under 15 m/s and the rotor under 30 rpm

The brake is fail-safe. The relay's normally-closed contacts short the generator phases (through brake resistors on bigger machines), and the Arduino has to hold the relay on (D7 HIGH) for the turbine to run. If the board loses power, crashes, or a wire breaks, the turbine brakes. It also starts braked at power-on.

The LCD shows wind, rpm, battery voltage and dump load (or the brake reason). Over USB it logs a CSV line every second:

DATA,seconds,wind_ms,rpm,batt_v,gen_v,dump_pct,state
DATA,42,7.3,312,13.62,18.4,0,RUN

Files

FileWhat it is
firmware/wind_turbine_controller/wind_turbine_controller.inoFirmware
firmware/build/wind_turbine_controller.hexReal-time build
firmware/build/wind_turbine_controller_sim_x10.hex5-minute brake release shortened to 30 s, for Proteus
test/sim_test.cSimulator test

Building it in Proteus

  1. Add ARDUINO UNO, LM016L, RELAY + NPN driver + diode, IRLZ44N + a power RES as the dump load, SW-SPST for STOP, and two POT-HG to stand in for the battery and generator dividers.
  2. For the anemometer and hall sensor, use CLOCK generators on D2 and D3. 11 Hz on D2 is about 7.3 m/s. 5 Hz on D3 is 300 rpm.
  3. Wire it as in images/wiring.png. Set the Arduino's Program File to firmware/build/wind_turbine_controller_sim_x10.hex.
  4. Run it. Turn the battery pot towards 14.6 V to see the dump load come in, then raise the D2 clock above 38 Hz (25 m/s) to see the storm brake.

Save it as proteus/wind-turbine-controller.pdsprj and commit it.

In the field

  • Size the dump load for the turbine's full rated power, with margin. A 1 kW turbine needs a 1 kW (or bigger) resistor, mounted where the heat can go.
  • Put a proper fuse and a DC breaker between the rectifier and the battery.
  • The anemometer should be on the tower but clear of the rotor wake (at least 1 m below the blade tip, or on a side arm).
  • Check the tower earthing and lightning protection. A turbine tower is usually the tallest thing around.

Testing

tools/test_all.sh runs the test. It checks start-up braked, the release, the dump load ramp at 14.6 and 15.0 V, that the turbine is never disconnected, storm braking with the gust tolerance, the 5-minute calm release, over-speed, the STOP switch, and the dump-load-overwhelmed case.